Home › All Refrigerants

All Refrigerant PT Charts

34 refrigerants with pressure-temperature saturation data. Every chart lists saturation pressure in PSIG, PSIA, kPa and bar in 5°F steps, calculated from NIST reference equations of state via CoolProp. Zeotropic blends with temperature glide also list vapor (dew) pressure. Use the vapor column for superheat and the liquid column for subcooling. GWP values are IPCC AR4 100-year figures, the basis used by the EPA's AIM Act rules.

Browse by type: HFC · HFO & low-GWP blends · Natural · Legacy / phased out · Side-by-side comparisons

Refrigerant Category Safety GWP ODP Boiling Pt Data Pts
R-12 CFC A1 10900 1.0 -21.6°F 59
R-123 HCFC B1 77 0.02 82.1°F 64
R-1233zd(E) HFO A1 4.5 0 64.9°F 62
R-1234yf HFO A2L 4 0 -21.1°F 53
R-1234ze(E) HFO A2L 7 0 -2.2°F 54
R-125 HFC A1 3500 0 -54.6°F 46
R-134a HFC A1 1430 0 -14.9°F 53
R-143a HFC A2L 4470 0 -53°F 48
R-152a HFC A2 124 0 -11.2°F 58
R-170 (Ethane) Natural / HC A3 6 0 -127.4°F 33
R-22 HCFC A1 1810 0.055 -41.5°F 57
R-227ea HFC A1 3220 0 2.6°F 51
R-23 HFC A1 14800 0 -115.6°F 31
R-236fa HFC A1 9810 0 29.3°F 54
R-245fa HFC B1 1030 0 59.1°F 58
R-290 (Propane) Natural / HC A3 3 0 -43.8°F 57
R-32 HFC A2L 675 0 -61°F 50
R-404A HFC Blend A1 3922 0 -51.2°F 48
R-407A HFC Blend A1 2107 0 -49°F 51
R-407C HFC Blend A1 1774 0 -46.5°F 53
R-407F HFC Blend A1 1825 0 -50.9°F 51
R-410A HFC Blend A1 2088 0 -60.6°F 48
R-422D HFC Blend A1 2729 0 -46.1°F 49
R-448A HFO/HFC Blend A1 1387 0 -50.6°F 52
R-449A HFO/HFC Blend A1 1397 0 -50.3°F 52
R-452A HFO/HFC Blend A1 2141 0 -52.6°F 50
R-454B HFO/HFC Blend A2L 467 0 -58.9°F 46
R-454C HFO/HFC Blend A2L 146 0 -50.0°F 50
R-502 CFC Blend A1 4657 0.33 -48.6°F 49
R-507A HFC Blend A1 3985 0 -52.1°F 47
R-513A HFO/HFC Blend A1 631 0 -20.6°F 53
R-600a (Isobutane) Natural / HC A3 3 0 10.9°F 60
R-717 (Ammonia) Natural B2L 0 0 -28°F 68
R-744 (CO₂) Natural A1 1 0 -126.5°F 32