R-410A PT Chart

A1 GWP 2088

Zeotropic blend (R-32/R-125, 50/50). HFC Blend.

Phase-down (replaced by R-454B for new equipment since Jan 2025)

Boiling Point
-60.6°F
-51.4°C
Critical Temp
160.4°F
71.3°C
Critical Pressure
710.9 psia
49.01 bar

About R-410A

R-410A has been the standard refrigerant in US residential split AC and heat pumps since R-22 was banned from new equipment in 2010. Since January 2025 new residential systems must use a refrigerant with GWP under 700, so most manufacturers switched to R-454B or R-32, but millions of installed R-410A systems will be serviced for years. It runs roughly 60% higher pressure than R-22, which is why gauges, hoses and recovery equipment must be rated for it.

Saturation pressures at typical operating points, taken from the table below:

The table covers -80°F to 155°F in 5°F steps. Below about -61°F the saturation pressure is below atmospheric, so gauges read in vacuum (shown in blue in the table).

R-410A Pressure-Temperature Graph

R-410A Saturation Pressure Table

Blue values indicate vacuum (below atmospheric pressure).

°F °C PSIG PSIA kPa bar
-80-62.2-6.58.2256.70.567
-75-59.4-5.19.6166.30.663
-70-56.7-3.511.1877.10.771
-65-53.9-1.712.9589.30.893
-60-51.10.214.94103.01.03
-55-48.32.517.17118.41.184
-50-45.65.019.65135.51.355
-45-42.87.722.4154.51.545
-40-40.010.825.45175.51.755
-35-37.214.128.82198.71.987
-30-34.417.832.52224.22.242
-25-31.721.936.58252.22.522
-20-28.926.341.03282.92.829
-15-26.131.245.88316.43.164
-10-23.336.551.17352.83.528
-5-20.642.256.91392.43.924
0-17.848.463.13435.34.353
5-15.055.269.86481.74.817
10-12.262.477.13531.85.318
15-9.470.384.95585.75.857
20-6.778.793.36643.76.437
25-3.987.7102.4706.07.06
30-1.197.4112.07772.77.727
351.7107.7122.43844.18.441
404.4118.8133.49920.49.204
457.2130.6145.281001.710.017
5010.0143.1157.841088.310.883
5512.8156.5171.211180.411.804
6015.6170.7185.41278.312.783
6518.3185.8200.471382.213.822
7021.1201.7216.431492.214.922
7523.9218.6233.331608.816.088
8026.7236.5251.211732.017.32
8529.4255.4270.11862.218.622
9032.2275.3290.031999.719.997
9535.0296.4311.062144.721.447
10037.8318.5333.232297.522.975
10540.6341.9356.582458.524.585
11043.3366.5381.152627.926.279
11546.1392.3406.992806.128.061
12048.9419.5434.172993.529.935
12551.7448.0462.733190.431.904
13054.4478.0492.733397.233.972
13557.2509.5524.243614.536.145
14060.0542.6557.333842.638.426
14562.8577.4592.084082.340.823
15065.6613.9628.594334.043.34
15568.3652.3666.964598.645.986

Properties

ASHRAE Designation410A
Safety ClassificationA1 (non-flammable, low toxicity)
GWP (AR4, 100-yr)2088
ODP0
Molecular Weight72.59 g/mol
Boiling Point (1 atm)-60.6°F / -51.4°C
Critical Temperature160.4°F / 71.3°C
Critical Pressure710.9 psia / 49.01 bar
CategoryHFC Blend

Common Applications

Frequently Asked Questions

What pressure should R-410A be at 70°F?

At 70°F (21.1°C), R-410A has a saturation pressure of 201.7 PSIG (216.4 PSIA, 1,492 kPa absolute). This is a common reference point HVAC technicians use to verify refrigerant charge.

What is normal R-410A suction pressure?

At a typical 45°F evaporator operating temperature, R-410A suction pressure is approximately 130.6 PSIG (118.8 PSIG at 40°F). Actual suction pressure depends on indoor load, airflow and outdoor temperature, so always calculate superheat rather than charging to a pressure.

Is R-410A being discontinued?

Yes. The EPA AIM Act requires all new residential and light commercial AC and heat pump equipment sold in the US after January 1, 2025 to use a lower-GWP refrigerant. R-410A systems already installed can continue to be serviced with R-410A indefinitely.

What refrigerant is replacing R-410A?

R-454B (sold as Puron Advance and Opteon XL41) is the primary replacement for R-410A in new US residential AC and heat pumps. It has a GWP of 467 — 78% lower than R-410A's 2088. R-32 is also approved and used widely in mini-splits globally.