Home › R-404A

R-404A PT Chart

A1 GWP 3922

Zeotropic blend (R-125/R-143a/R-134a). HFC Blend.

Phase-down (high GWP)

Boiling Point
-51.2°F
-46.2°C
Critical Temp
161.8°F
72.1°C
Critical Pressure
541.7 psia
37.35 bar

About R-404A

R-404A has been the workhorse of US commercial refrigeration, including walk-in freezers, reach-ins, ice machines and supermarket racks. Its GWP of 3922 puts it at the top of the EPA's phase-down list, and new systems are moving to R-448A, R-449A, R-454C, CO₂ and propane. Its glide is only about 1°F, so the liquid and vapor columns are nearly identical.

Saturation pressures at typical operating points, taken from the table below:

The table covers -80°F to 155°F in 5°F steps. Below about -51°F the liquid saturation pressure is below atmospheric, so gauges read in vacuum (shown in blue in the table).

R-404A Pressure-Temperature Graph (Bubble & Dew)

R-404A Saturation Pressure Table

R-404A is a zeotropic blend with temperature glide, so it has two saturation pressures at each temperature. Use Vapor (dew) PSIG to find evaporator saturation for superheat, and Liquid (bubble) PSIG to find condenser saturation for subcooling. PSIA, kPa and bar columns are liquid (bubble) pressures. Blue values indicate vacuum.

°F °C Liquid PSIG
(bubble)
Vapor PSIG
(dew)
PSIA kPa bar
-80-62.2-8.3-8.66.3743.90.439
-75-59.4-7.3-7.67.4451.30.513
-70-56.7-6.0-6.48.6659.70.597
-65-53.9-4.7-5.110.0269.10.691
-60-51.1-3.1-3.611.5679.70.797
-55-48.3-1.4-1.913.2791.50.915
-50-45.60.5-0.115.17104.61.046
-45-42.82.62.017.28119.21.192
-40-40.04.94.319.62135.31.353
-35-37.27.56.822.2153.11.531
-30-34.410.39.625.03172.61.726
-25-31.713.412.728.14194.01.94
-20-28.916.816.031.53217.42.174
-15-26.120.519.735.23242.92.429
-10-23.324.623.639.26270.72.707
-5-20.628.927.943.63300.83.008
0-17.833.732.648.36333.43.334
5-15.038.837.753.47368.63.686
10-12.244.343.158.98406.64.066
15-9.450.249.064.91447.54.475
20-6.756.655.371.28491.54.915
25-3.963.462.178.12538.65.386
30-1.170.769.385.43589.05.89
351.778.677.193.25643.06.43
404.486.985.4101.6700.57.005
457.295.894.2110.49761.87.618
5010.0105.3103.6119.96827.18.271
5512.8115.3113.6130.02896.48.964
6015.6126.0124.2140.7970.19.701
6518.3137.3135.5152.021048.110.481
7021.1149.3147.4164.011130.811.308
7523.9162.0160.1176.691218.212.182
8026.7175.4173.4190.091310.613.106
8529.4189.5187.5204.241408.214.082
9032.2204.5202.4219.171511.115.111
9535.0220.2218.1234.91619.616.196
10037.8236.8234.7251.471733.817.338
10540.6254.2252.1268.911854.118.541
11043.3272.6270.4287.251980.519.805
11546.1291.8289.7306.532113.421.134
12048.9312.1309.9326.782253.122.531
12551.7333.4331.2348.052399.723.997
13054.4355.7353.6370.382553.725.537
13557.2379.1377.0393.822715.327.153
14060.0403.7401.7418.432885.028.85
14562.8429.6427.7444.293063.230.632
15065.6456.8455.0471.473250.732.507
15568.3485.4—500.113448.234.482

Properties

ASHRAE Designation404A
Safety ClassificationA1 (non-flammable, low toxicity)
GWP (AR4, 100-yr)3922
ODP0
Molecular Weight97.6 g/mol
Boiling Point (1 atm)-51.2°F / -46.2°C
Critical Temperature161.8°F / 72.1°C
Critical Pressure541.7 psia / 37.35 bar
CategoryHFC Blend

Common Applications

Frequently Asked Questions

What pressure should R-404A be at 70°F?

At 70°F, R-404A has a saturation pressure of 149.3 PSIG (164.0 PSIA). Typical R-404A suction pressure at −20°F (freezer evaporator) is about 16.8 PSIG, and at 0°F is about 33.7 PSIG.

What is replacing R-404A in commercial refrigeration?

R-449A (Opteon XP40) is the primary low-GWP replacement for R-404A and R-507A. At 70°F, R-449A has a nearly identical pressure (151.0 vs 149.3 PSIG). GWP drops from 3922 to 1397 — a 64% reduction.

Is R-404A still available?

R-404A is still available in the US for servicing existing equipment, but faces HFC phasedown under the EPA AIM Act due to its high GWP (3922). Most new commercial refrigeration equipment now uses R-449A, R-448A, or natural refrigerants.