R-32 PT Chart

A2L GWP 675

Pure refrigerant (Difluoromethane). HFC.

Boiling Point
-61.0°F
-51.7°C
Critical Temp
172.6°F
78.1°C
Critical Pressure
838.7 psia
57.83 bar

About R-32

R-32 is a single-component HFC that makes up half of R-410A. Daikin and several other manufacturers use it straight in mini-splits and, increasingly, ducted systems, because it has a GWP of 675 and better heat transfer than R-410A. It has no glide, so one pressure column applies to both superheat and subcooling, but it runs slightly higher pressure and higher discharge temperatures than R-410A and is classified A2L.

Saturation pressures at typical operating points, taken from the table below:

The table covers -80°F to 165°F in 5°F steps. Below about -61°F the saturation pressure is below atmospheric, so gauges read in vacuum (shown in blue in the table).

R-32 Pressure-Temperature Graph

R-32 Saturation Pressure Table

Blue values indicate vacuum (below atmospheric pressure).

°F °C PSIG PSIA kPa bar
-80-62.2-6.48.3157.30.573
-75-59.4-5.09.7267.00.67
-70-56.7-3.411.377.90.779
-65-53.9-1.613.0990.30.903
-60-51.10.415.11104.11.041
-55-48.32.717.35119.71.197
-50-45.65.219.86136.91.369
-45-42.88.022.65156.11.561
-40-40.011.025.73177.41.774
-35-37.214.429.14200.92.009
-30-34.418.232.89226.72.267
-25-31.722.337.0255.12.551
-20-28.926.841.51286.22.862
-15-26.131.746.43320.13.201
-10-23.337.151.8357.13.571
-5-20.642.957.63397.33.973
0-17.849.363.95440.94.409
5-15.056.170.79488.14.881
10-12.263.578.18539.05.39
15-9.471.486.14593.95.939
20-6.780.094.71653.06.53
25-3.989.2103.92716.57.165
30-1.199.1113.79784.67.846
351.7109.7124.35857.48.574
404.4121.0135.65935.39.353
457.2133.0147.71018.310.183
5010.0145.8160.541106.911.069
5512.8159.5174.211201.212.012
6015.6174.0188.741301.313.013
6518.3189.5204.171407.714.077
7021.1205.8220.521520.515.205
7523.9223.2237.851639.916.399
8026.7241.5256.181766.317.663
8529.4260.9275.561899.918.999
9032.2281.3296.022041.020.41
9535.0302.9317.612189.821.898
10037.8325.7340.372346.823.468
10540.6349.6364.342512.125.121
11043.3374.9389.582686.126.861
11546.1401.4416.132869.128.691
12048.9429.3444.043061.530.615
12551.7458.7473.373263.832.638
13054.4489.5504.173476.134.761
13557.2521.8536.523699.136.991
14060.0555.8570.473933.239.332
14562.8591.4606.14178.941.789
15065.6628.8643.514436.944.369
15568.3668.1682.84707.747.077
16071.1709.4724.094992.449.924
16573.9752.9767.575292.252.922

Properties

ASHRAE Designation32
Safety ClassificationA2L (mildly flammable)
GWP (AR4, 100-yr)675
ODP0
Molecular Weight52.02 g/mol
Boiling Point (1 atm)-61.0°F / -51.7°C
Critical Temperature172.6°F / 78.1°C
Critical Pressure838.7 psia / 57.83 bar
CategoryHFC

Common Applications

Frequently Asked Questions

What pressure should R-32 be at 70°F?

At 70°F, R-32 has a saturation pressure of 205.8 PSIG (220.5 PSIA), slightly higher than R-410A (201.7 PSIG). R-32 is a single-component refrigerant with no temperature glide, making servicing straightforward.

What equipment uses R-32 refrigerant?

R-32 is the primary refrigerant in modern mini-split systems from Daikin, Mitsubishi, and other manufacturers. It is also used in many new ducted split systems. R-32 has a GWP of 675 — about 68% lower than R-410A's 2088.

Is R-32 safe to use?

R-32 is classified A2L (mildly flammable, low burning velocity). It requires A2L-rated service equipment and follows ASHRAE 15 safety guidelines. R-32 should not be used as a replacement refrigerant in R-410A equipment — systems must be designed for R-32.